CP1E Acc Instruction for Servo
|CP1E Acc Instruction for Servo
ACC(888) starts pulse output on the port specified 00 using the mode specified and using the target frequency and acceleration/deceleration rate. The frequency is increased every pulse control period (4 ms) at the acceleration rate specified in D0 until the target frequency specified inD1 is reached.